PCE Instruments PCE-WMM 50-ICA Gas Test Instrument for CO2 with 2 configurable alarm thresholds and 4-digit digital display
(Incl. Tax: €709.92)
The PCE-WMM 50-ICA CO2 gas transducer is an economical device with an integrated alarm for detecting carbon dioxide (CO2), ideal for protecting against colourless and odourless gases that are hazardous to health. It is mainly used in sectors such as the food industry, metallurgy, chemistry and waste management. Consisting of two parts, the transducer is placed in the hazardous areas, while the control unit is located outside. The system offers two adjustable alarm levels and triggers an optical and acoustic warning when the measured value exceeds a preset threshold.
The CO2 gas transmitter PCE-WMM 50-ICA is equipped with a 4-digit digital display and 4 LEDs, allowing constant visual monitoring of gas concentrations. The potential-free switching output is easy to access and allows other alarm devices to be activated, suction motors to be turned on, or machinery to be stopped. The CO2 gas transmitter PCE-WMM 50 can be easily installed on a wall. Carbon dioxide is harmful to the human body, even in small doses. Even at concentrations of 0.3%, it can be detrimental. If the value reaches 5%, it can cause headaches and dizziness. Values around or above 8% can cause fainting or even death.
| Main Unit with CO2 Sensor | |
| CO2 Measurement Range | 0 ... 50,000 ppm (5% vol.) |
| Resolution | 0 ... 9,999 ppm: 10 ppm 1 ... 5% vol.: 0.1% |
| Accuracy | ±100 ppm or ±5% of the measurement |
| Repeatability | ±20 ppm at 400 ppm |
| Sensor Drift | <20 ppm/year at 400 ppm |
| Response Time | t90 <60 s |
| Warm-up Time | <60 s at 22°C |
| CO2 Sensor | NDIR |
| Measurement Principle | Diffusion Measurement |
| Temperature Measurement Range (Gas/Ambient) |
0 ... +45 ºC |
| Resolution | 0.1°C |
| Accuracy | ± 1°C |
| Temperature Units | °C / °F |
| Acoustic Alarm | 80 dBA |
| Optical Alarms/Status Indicators | 4 LEDs: operation, alarm 1 and 2, error |
| Alarm Relay | SPST normally open: 30V DC / 250V AC, max 2A |
| Alarm Limit | Alarm 1: 0.5 / 1 / 1.5 / 2 % Alarm 2: 1.5 / 2 / 2.5 / 3 / 3.5 / 4 % |
| Menu Items | Functional check of the connection between the main unit and control unit Calibration Changing the unit of measurement from ºC to ºF Alarm 1, 2, and factory settings |
| Display | LCD 4 digits: in the range 0 ... 9,999 ppm 3 digits in the range 1 ... 5% 3 digits for temperature display |
| Controls | Reset, menu selection, Enter |
| Safety | Continuous self-check of temperature, sensor life, inconsistent measurements, EEPROM system, internal data transfer |
| Power Supply | Wall power adapter 6V / 0.5A 100 ... 240V AC, 50/60 Hz |
| Power Consumption | 1W at 115V AC / 60 Hz 2W at 230V AC / 50 Hz |
| Operating Conditions | 0 ... 40°C / Max 95% RH |
| Storage Conditions | -20 ... 60°C / Max 95% RH |
| Housing | Plastic |
| Protection Rating | IP54 (splash-proof) |
| Dimensions | 168 x 125 x 47 mm (without connections) |
| Weight | Approximately 450 g |
| Control Unit | |
| Temperature (gas/ambient) | 0 ... +45°C |
| Acoustic Alarm | 80 dBA |
| Optical Alarms/Status Indicators | 4 LEDs: operation, alarm 1 and 2, error |
| Display | LCD 4 digits: in the range 0 ... 9,999 ppm 3 digits in the range 1 ... 5% 3 digits for temperature display |
| Menu Items | Functional check of the connection between the main unit and the control unit Changing the unit of measurement from ºC to ºF |
| Controls | Functional test, reset, menu selection, Enter, switch from °C to °F |
| Power Supply | Through connection to the main unit |
| Housing | Plastic |
| Dimensions | 118 x 85 x 34 mm (without connections) |
| Weight | Approximately 130 g |
- ISO certification included
- Carbon dioxide (CO2) detection
- 2 adjustable alarm limits
- 4-digit digital display
- Constant visual monitoring
- Potential-free contacts
- Integrated alarm device
- 3-component system
Delivery Contents:
1 x CO2 Gas Transmitter PCE-WMM 50
1 x RJ45 Connector
1 x RJ45 Connection Cable
1 x Wall Power Adapter
1 x ISO Certification (English/German)
Operating Instructions (available for download)
- EAN Code:
- 4250348727107
- Typology:
- Gas detector
- Brand:
- PCE INSTRUMENTS
- Resolution (mm):
- 10 ppm
- Measurements range:
- 0 - 50000 ppm